Tier 460 Terminal Block Motor Surge Protection
Shunt Trip Controller Device
1 - 7
<
>
The Tier 460 Terminal Block Motor Surge Protection Shunt Trip Controller Device will protect a motor, or an entire system, from power quality events. It runs an onboard surge protection device in parallel with an onboard shunt trip controller. The shunt trip controller will send a signal, at predetermined levels, to a shunt trip breaker located on a panel, or at the system or motor, and force it to disconnect the load. Please note, shunt trips require a manual reset after a disconnection event.
The onboard SPD remains online while the load is disconnected.
Available for 120V or 240V breakers.
The 460 SPD family is the ideal solution for protecting industrial systems, motors, and equipment from the damaging effects of transients, phase loss, voltage sags and swells.
The 460 Terminal Block Motor Surge Protection Shunt Trip Controller Device features the industry's most advanced metal oxide varistor (MOV) technology.
Its thermally protective, and arc extinguishing, design has a significant advantage when subjected to abnormal over-voltage and high fault current.
The multiple MOV technology allows for the continuation of protection even after a module failure (indicated by our dual color LEDs), giving critical time, under reduced protection, for a repair or replacement (This is covered by our 10 year warranty).
Transient impulses can significantly impact your facility’s power quality, easily disrupting or damaging your process or equipment. While its important to protect against high-energy events, a more frequent, yet often overlooked power quality concern is the damage caused by a phase loss, a temporary voltage sag or a voltage swell condition. Disconnecting your sensitive loads during these longer duration power quality events is the easiest way to safeguard important equipment.
*Please note, this unit may look similar in size to our Modular Terminal Block SPD, but it is not the same size, this enclosure and its mounting footprint are larger. Please see the dimensional drawing for space planning purposes.
For custom specifications, please contact the factory. We will be happy to accommodate your needs.
Features:
Surge
• Thermally Protected MOV
Surge Levels Available:
• 50 kA/Mode - 150 kA/Mode
• ANSI/UL 1449 4th Edition, CSA
• Sine Wave Tracking: Type 2 only
• Surge Impulse Rated & Tested
Enclosure
•NEMA 4 Indoor/Outdoor Rated
•14 Gauge Steel
•Stainless Steel Door Clamps, Continuous Hinge, and Hinge Pin
•Oil Resistant Gasket
•External Welded on Mounting Brackets
•Terminal Block Configuration
Monitoring & Control
• Monitors:Under/Over Voltage, Phase
Loss, Imbalance
• Dual Color(Blue/Red) LEDS
• Audible Alarm w/ disable switch
• Form C Relays
• Active Load Disconnect & Reset
• User Selectable Controls Over & Under Voltage:
+/- 5, 7.5 10,15, 20, 25%
General Technical Specifications | |
---|---|
Connection Type | Parallel |
Maximum Continuous Operating Voltage | 120V, 150 VAC; 240V, 300 VAC; 277V, 320 VAC; 480V, 550 VAC; 125%, All Others 115% |
Short Circuit Rating | 200kAIC |
Protection Modes | All Connected Modes: L-N, L-L, L-G, N-G |
Operating Frequency Range | 47 - 63 Hz |
UL 1449 Location Type | Type 1/Type 2 |
UL 1449 Nominal Discharge Current (In) | 20 kA |
Connection | Terminal Block |
Status Indication | Dual Color LEDs, Form C, Surge Counter, Audible Alarm w/disable switch, Under Voltage/ Overvoltage, Phase Loss |
Enclosure | NEMA 4 Indoor/Outdoor rated (14 gauge steel) |
50 Ohm EMI/RFI Attenuation (Only available on Type 2) | 60/40dB Max |
Response Time | <0.5 nanoseconds |
Operating Temperature | -40 C to +75 C |
Operating Humidity | 0% to 95% non-condensing |
Unit Size (Height x Width x Depth) | |
Modular: Up to 150 kA /Mode | 17.50" x 14.94" x 6.00" |
Warranty | 10 Years |
307 Chaumont Dr. │ Endwell, NY 13760 │ Phone: 607-484-1212 │ Toll-Free: 866-748-2357
SOUTHERN TIER TECHNOLOGIES © 2017 - 2022
3